低(di)壓智(zhi)能電(dian)(dian)(dian)容補償(chang)裝置為改善供(gong)(gong)電(dian)(dian)(dian)功率因數、提高電(dian)(dian)(dian)網效(xiao)率提供(gong)(gong)解(jie)決方案。該產品的主要(yao)應用(yong)領域有:電(dian)(dian)(dian)力配電(dian)(dian)(dian)系統 、工業配電(dian)(dian)(dian)系統 、市政商業建筑(zhu)及小(xiao)區配電(dian)(dian)(dian)系統 、軌(gui)道(dao)交通配電(dian)(dian)(dian)系統、箱變(bian)、成套(tao)柜、戶(hu)外配電(dian)(dian)(dian)箱、兩(liang)網JP柜招標等。為了更好的展示智(zhi)能電(dian)(dian)(dian)容補償(chang)方案的優勢,我們用(yong)一(yi)個表格做對(dui)比分(fen)析:
醫院配電系統補(bu)償(chang)模組(zu)的成因、性(xing)質及對其進行的補(bu)償(chang)
安裝(zhuang)接線(xian)之前一定(ding)要先看清楚電(dian)容補償裝(zhuang)置(zhi)柜上配(pei)置(zhi)的(de)(de)(de)(de)控(kong)制(zhi)器的(de)(de)(de)(de)安裝(zhuang)接線(xian)圖,即:控(kong)制(zhi)器的(de)(de)(de)(de)工作電(dian)源有220V、380V,分清檢測信號是取同(tong)(tong)相(xiang)還是不同(tong)(tong)相(xiang),取樣用的(de)(de)(de)(de)電(dian)流(liu)互(hu)感器一般(ban)都是采用LMZJ1-0.5/5系列的(de)(de)(de)(de),要穿在低壓負(fu)(fu)荷(he)(he)的(de)(de)(de)(de)總電(dian)流(liu)側,電(dian)流(liu)互(hu)感器的(de)(de)(de)(de)一次(ci)側電(dian)流(liu)的(de)(de)(de)(de)容量(liang)選擇,要根(gen)據該配(pei)變低壓側總負(fu)(fu)荷(he)(he)的(de)(de)(de)(de)120-150%來確定(ding),否(fou)則,該控(kong)制(zhi)器是不能正確動作的(de)(de)(de)(de)。
現在用電(dian)(dian)(dian)設(she)(she)備(bei)有(you)很多(duo),如(ru)電(dian)(dian)(dian)子、中(zhong)頻(pin)、變頻(pin)等設(she)(she)備(bei),會(hui)產生(sheng)諧(xie)波(bo)(bo)(bo)(bo)。有(you)了諧(xie)波(bo)(bo)(bo)(bo),電(dian)(dian)(dian)流、電(dian)(dian)(dian)壓(ya)(ya)、波(bo)(bo)(bo)(bo)形發生(sheng)畸(ji)變,損(sun)壞電(dian)(dian)(dian)力(li)電(dian)(dian)(dian)容器(qi)、接觸器(qi)、熔(rong)斷器(qi),嚴重時會(hui)引起火災,燒毀用電(dian)(dian)(dian)設(she)(she)備(bei)。解決方(fang)法(fa):1、諧(xie)波(bo)(bo)(bo)(bo)不嚴重的提(ti)高(gao)電(dian)(dian)(dian)容器(qi)電(dian)(dian)(dian)壓(ya)(ya)等級。2、諧(xie)波(bo)(bo)(bo)(bo)嚴重的要配置(zhi)抗(kang)諧(xie)波(bo)(bo)(bo)(bo)的電(dian)(dian)(dian)抗(kang)器(qi),但這種電(dian)(dian)(dian)抗(kang)器(qi)的造(zao)價相對比(bi)較高(gao)。